>>>Air cooled heat pump modular unit

Air cooled heat pump modular unit

  • Using environmental protection R407C, and will not destroy the ozone layer
  • Main control design of any module: any module can be used as the main module as long as the hand operator is plugged in.
  • Ultra strong compatibility: The same and different models can also be combined in any combination, it can be up to 8 modules
  • Ultra strong protection: the safety protection function is complete, has the strong fault self-diagnosis function.
  • Balanced operation: Balanced operation technology between compressors, ensure the rotation of every compressor in the system, greatly extend the service life of the compressor.
  • Remote monitoring function: Built-in RS485 communication, user can choose cloud interface and connect phone to check machine data.

Description

  1. Represent air-cooled chilled water unit series
  2. Indicatenominal refrigerating capacity of unit
  3. Blank: single cool unit; H= with heat pump faction
  4. M= Modular unit
  5. Blank: no heat recovery  R= with heat recovery
  6. Percentage of heat recovery
  • Using environmental protection R407C, and will not destroy the ozone layer
  • Main control design of any module: any module can be used as the main module as long as the hand operator is plugged in.
  • Ultra strong compatibility: The same and different models can also be combined in any combination, it can be up to 8 modules
  • Ultra strong protection: the safety protection function is complete, has the strong fault self-diagnosis function.
  • Balanced operation: Balanced operation technology between compressors, ensure the rotation of every compressor in the system, greatly extend the service life of the compressor.
  • Remote monitoring function: Built-in RS485 communication, user can choose cloud interface and connect phone to check machine data.
Model AC019H-MH AC028H-MH AV038H-MH
Refrigerating capacity kW 65 104 130
Refrigerating input power kW 20.3 31.6 40.6
Heating capacity kW 75 114 150
Heating input power kW 20.6 32.71 41.2
Refrigerating rated current A 39.38 66.64 78.76
Heating rated current A 39.76 67.96 79.52
Electric 380V-3ph-50Hz
Water side heat
exchanger
Type Efficient shell and tube type
Refrigerated water flow m³/h 11.2 17.9 22.39
Heat water flow m³/h 12.9 19.6 25.83
Inlet and outlet pipe diameter DN 100 100 100
Water Pressure Drop kPa <50 <50 <50
Water side pressure-bearing MPa 1.05
Compressor Type Scroll compressor
Fan Air volume m³/h 30000 46000 60000
QTY pcs 2 2 4
Refrigerant Type R410A
Refrigerating system QTY 2
Dimensions Length mm 2000 2000 2000
Breadth mm 1000 1200 2000
Height mm 2250 2250 2250
Unit transportation weight kg 730 1100 1460

Remark:

1.nominal refrigerating condition: inflow and outflow of chilled water temperature 7/12℃, ambient dry bulb temperature35℃;

2.nominal heating condition: inflow and outflow of hot water temperature 40/45℃, ambient dry/wet bulb temperature7/6℃;

3.water-side fouling factor: 0.018m2.k/kw.

Get Quote