- Using environmental protection R407C, and will not destroy the ozone layer
- Main control design of any module: any module can be used as the main module as long as the hand operator is plugged in.
- Ultra strong compatibility: The same and different models can also be combined in any combination, it can be up to 8 modules
- Ultra strong protection: the safety protection function is complete, has the strong fault self-diagnosis function.
- Balanced operation: Balanced operation technology between compressors, ensure the rotation of every compressor in the system, greatly extend the service life of the compressor.
- Remote monitoring function: Built-in RS485 communication, user can choose cloud interface and connect phone to check machine data.
Air cooled heat pump modular unit
Description
- Represent air-cooled chilled water unit series
- Indicatenominal refrigerating capacity of unit
- Blank: single cool unit; H= with heat pump faction
- M= Modular unit
- Blank: no heat recovery R= with heat recovery
- Percentage of heat recovery
- Using environmental protection R407C, and will not destroy the ozone layer
- Main control design of any module: any module can be used as the main module as long as the hand operator is plugged in.
- Ultra strong compatibility: The same and different models can also be combined in any combination, it can be up to 8 modules
- Ultra strong protection: the safety protection function is complete, has the strong fault self-diagnosis function.
- Balanced operation: Balanced operation technology between compressors, ensure the rotation of every compressor in the system, greatly extend the service life of the compressor.
- Remote monitoring function: Built-in RS485 communication, user can choose cloud interface and connect phone to check machine data.
Model | AC019H-MH | AC028H-MH | AV038H-MH | ||
Refrigerating capacity | kW | 65 | 104 | 130 | |
Refrigerating input power | kW | 20.3 | 31.6 | 40.6 | |
Heating capacity | kW | 75 | 114 | 150 | |
Heating input power | kW | 20.6 | 32.71 | 41.2 | |
Refrigerating rated current | A | 39.38 | 66.64 | 78.76 | |
Heating rated current | A | 39.76 | 67.96 | 79.52 | |
Electric | 380V-3ph-50Hz | ||||
Water side heat exchanger |
Type | Efficient shell and tube type | |||
Refrigerated water flow | m³/h | 11.2 | 17.9 | 22.39 | |
Heat water flow | m³/h | 12.9 | 19.6 | 25.83 | |
Inlet and outlet pipe diameter | DN | 100 | 100 | 100 | |
Water Pressure Drop | kPa | <50 | <50 | <50 | |
Water side pressure-bearing | MPa | 1.05 | |||
Compressor | Type | Scroll compressor | |||
Fan | Air volume | m³/h | 30000 | 46000 | 60000 |
QTY | pcs | 2 | 2 | 4 | |
Refrigerant | Type | R410A | |||
Refrigerating system QTY | 2 | ||||
Dimensions | Length | mm | 2000 | 2000 | 2000 |
Breadth | mm | 1000 | 1200 | 2000 | |
Height | mm | 2250 | 2250 | 2250 | |
Unit transportation weight | kg | 730 | 1100 | 1460 | |
Remark: 1.nominal refrigerating condition: inflow and outflow of chilled water temperature 7/12℃, ambient dry bulb temperature35℃; 2.nominal heating condition: inflow and outflow of hot water temperature 40/45℃, ambient dry/wet bulb temperature7/6℃; 3.water-side fouling factor: 0.018m2.k/kw. |