- Horizontal concealed fan coil is hidden in the ceiling. The air volume range is 340~2380m3/h. The cooling capacity range is 1.8~12.6kW. The common high static pressure is 30Pa and the special high static pressure is up to 50Pa. Among them FP-WAC4 is four tube type, FP-WAT7 is large-temperature difference cooling condition, FPG-WA is a dry fan coil unit.
Horizontal concealed Fan Coil Unit
Description
Feature or Static Pressure: C4-four tube type, T7-large temperature difference, G30: 30Pa/G50: 50 Pa.
Installation type: A-concealed, M-surface.
Structure: W-Horizontal, L-Vertical, TK-ceilling
Nominal air volume: Number × 10m3 / h
FP- standard fan coil: FPG stands for dry fan coil
Index | Project | FP-34 | FP-51 | FP-68 | FP-85 | FP-102 | FP-136 | FP-170 | FP-204 | FP-238 | |
Rated air flow | H | m3/h | 340 | 510 | 680 | 850 | 1020 | 1360 | 1700 | 2040 | 2380 |
M | m3/h | 250 | 380 | 510 | 630 | 760 | 1020 | 1270 | 1530 | 1780 | |
L | m3/h | 170 | 250 | 340 | 420 | 510 | 680 | 850 | 1020 | 1190 | |
Rated cooling capacity | H | W | 1800 | 2700 | 3600 | 4500 | 5400 | 7200 | 9000 | 10800 | 12600 |
M | W | 1590 | 2300 | 3160 | 3900 | 4600 | 6330 | 7750 | 9200 | 10800 | |
L | W | 1260 | 1800 | 2520 | 3100 | 3700 | 5040 | 6200 | 7300 | 8700 | |
Heat | H | W | 2700 | 4050 | 5400 | 6750 | 8100 | 10800 | 13500 | 16200 | 18900 |
Input power | LSP | W | 37 | 52 | 62 | 76 | 96 | 134 | 152 | 189 | 228 |
30Pa | W | 44 | 59 | 72 | 87 | 108 | 156 | 174 | 212 | 253 | |
Unit noise | LSP | dB(A) | 37 | 39 | 41 | 43 | 45 | 46 | 48 | 50 | 52 |
30Pa | dB(A) | 40 | 42 | 44 | 46 | 47 | 48 | 50 | 52 | 54 | |
Coil | Model | Φ9.52 Copper Tube through Aluminum fins / 3 rows of 8 holes / Standard sheet distance | |||||||||
WF | kg/h | 310 | 465 | 620 | 775 | 930 | 1240 | 1550 | 1850 | 2160 | |
WR | kPa | 30 | 33 | 33 | 33 | 44 | 44 | 44 | 44 | 55 | |
Fan | Model | Φ160 double inlet centrifugal fan | |||||||||
QTY | SET | 1 | 1 | 2 | 2 | 2 | 3 | 4 | 4 | 4 | |
Motor | Model | Single-phase capacitor running three-speed motor | |||||||||
QTY | SET | 1 | 1 | 1 | 1 | 1 | 2 | 2 | 2 | 2 | |
Interface | Water pipe Interface | Water in/ out pipe: 3/4" inside thread /Condensing water pipe: 3/4" outside thread | |||||||||
Electrical Interface | Terminals ( five core wire high / medium / low / zero / ground ) | ||||||||||
WGT/kg | Standard | 12 | 13 | 17 | 18 | 19 | 26 | 29 | 33 | 36 | |
With return air box | 14 | 15 | 20 | 21 | 23 | 31 | 34 | 38 | 42 | ||
LA | 20 | 21 | 25 | 27 | 29 | 38 | 46 | 50 | 52 | ||
LM | 21 | 22 | 23 | 26 | 27 | 31 | 34 | 40 | 43 | ||
WM | 21 | 22 | 23 | 26 | 27 | 31 | 34 | 40 | 43 | ||
TK | 21 | 22 | 22 | 26 | 27 | 28 | 33 | 33 | 34 | ||
Remark: LSP(low static pressure); WF(Water flow); WR(water resistance) ◆ Technical Description: 1. Date under cooling condition: Air inlet DB/WB: 27/19.5℃; water inlet temperature 7℃; the temperature difference 5 ℃. 2. The cooling capacity of the unit: surface air cooler: 2.12mm standard slice distance; Adjust the slice distance to change the heat transfer area, the cooling capacity can be changed. 3. Date under heating condition: Air inlet DB/WB: DB21℃; water inlet temperature 60℃. The same water condition as refrigeration. 4. Unit noise: One meter measurement in front of and below the unit. The high static pressure unit needs to be installed with a return air duct. It is controlled at the air outlet after controlling the static pressure. 5. The above date complies with 12Pa low static pressure of external unit and 30Pa high static pressure . If the users need 50Pa high static, pls specify. |
FP- | 34WA | 51WA | 68WA | 85WA | 102WA | 136WA | 170WA | 204WA | 238WA |
A | 750 | 750 | 950 | 1050 | 1150 | 1450 | 1590 | 1790 | 1990 |
B | 420 | 485 | 685 | 785 | 885 | 1185 | 1310 | 1510 | 1710 |
C | 450 | 515 | 715 | 815 | 915 | 1215 | 1340 | 1540 | 1740 |