>>>Vertical Concealed Fan Coil Unit

Vertical Concealed Fan Coil Unit

  • The vertical concealed fan coil is hidden in the wall channel or walkway. The air volume range is 340~2380m3/h. The cooling capacity is from 1.8~12.6kW. The common high static pressure is 30Pa and the special high static pressure is up to 50Pa. Without four tube type fan coil unit, can be used directly for large temperature difference conditions. Also can provide dry fan coil unit.
Categories: ,

Description

Feature or Static Pressure: C4-four tube type, T7-large temperature difference, G30: 30Pa/G50: 50 Pa.

Installation type: A-concealed, M-surface.

Structure: W-Horizontal, L-Vertical, TK-ceilling

Nominal air volume: Number × 10m3 / h

FP- standard fan coil: FPG stands for dry fan coil

Index Project -34WAC4 -51WAC4 -68WAC4 -85WAC4 -102WAC4 -136WAC4 -170WAC4 -204WAC4 -238WAC4
Rated air flow H m3/h 340 510 680 850 1020 1360 1700 2040 2380
M m3/h 250 380 510 630 760 1020 1270 1530 1780
L m3/h 170 250 340 420 510 680 850 1020 1190
Rated cooling capacity H W 1800 2700 3600 4500 5400 7200 9000 10800 12600
M W 1590 2300 3160 3900 4600 6330 7750 9200 10800
L W 1260 1800 2520 3100 3700 5040 6200 7300 8700
Hot coil heat H W 1450 2160 2880 3600 4320 5400 6600 7600 8800
M W 1260 1880 2500 3130 3750 4700 5740 6610 7650
L W 1010 1510 2010 2520 3020 3780 4620 5320 6160

Input

power

LSP W 37 52 62 76 96 134 152 189 228
30Pa W 44 59 72 87 108 156 174 212 253
Unit noise LSP dB(A) 37 39 41 43 45 46 48 50 52
30Pa dB(A) 40 42 44 46 47 48 50 52 54
Cold water coil Model Φ9.52 Copper Tube through Aluminum fins / 3 rows of 8 holes / Standard Sheet Distance
WF kg/h 310 465 620 775 930 1240 1550 1850 2160
WR kPa 30 33 33 33 44 44 44 44 55
Hot water coil Model Φ9.52 Copper Tube through Aluminum fins / 3 rows of 8 holes / Standard Sheet distance
WF kg/h 250 370 495 620 743 930 1140 1300 1510
WR kPa 30 40 50 60 70 75 80 85 90
Fan Model Φ160 double inlet centrifugal fan
QTY SET 1 1 2 2 2 3 4 4 4
Motor Model Single-phase capacitor running three-speed motor
QTY SET 1 1 1 1 1 2 2 2 2
Interface Water pipe Interface Water in/ out pipe: 3/4" inside thread/Condensing water pipe: 3/4" outside thread
Electrical Interface Terminals ( five core wire high / medium / low / zero / ground )
WGT/kg Standard 13 14 18 20 21 28 31 35 38
With return air box 15 16 21 23 25 33 36 40 44

Remark:  LSP(low static pressure); WF(Water flow); WR(water resistance)

 Technical Description:

1. Date under cooling condition: Air inlet DB/WB: 27/19.5℃; water inlet temperature 7℃; the temperature difference 5 ℃.

2. The cooling capacity of the unit: surface air cooler: 2.12mm standard slice distance; Adjust the slice distance to change the heat transfer area, the cooling capacity can be changed.

3. Date under heating condition: Air inlet DB/WB: DB21℃; water inlet temperature 60℃; the temperature difference 5 ℃. The same water condition as refrigeration.

4. Unit noise: One meter measurement in front of and below the unit.

5. The above date complies with 12Pa low static pressure of external unit and 30Pa high static pressure . If the users need 50Pa high static, pls specify.

Installation Dimension Chart of Vertical Concealed Fan Coil Unit

FP- 34LA 51LA 68LA 85LA 102LA 136LA 170LA 204LA 238LA
A 695 760 960 1060 1180 1470 1590 1790 1990
B 595 660 860 960 1080 1370 1490 1690 1890
C 545 610 810 910 1010 1320 1440 1640 1840