Air Cooled Heat Pump Chiller Unit

  • Using environmental protection R407C or R134a, OPD value is zero, and will not destroy the ozone layer.
  • The condenser heat exchange tube adopts 5mm diameter copper tube, which is more efficient, and greatly reduce the amount of refrigerant filling.
  • It only needs to connect the chilled water pipe and power supply on site, which can effectively shorten the installation period.
  • COP of fallingfilm type unit is up to 3.4 or above, it can meet first level energy efficiency standards.
  • Stepless energy regulation, accurate control of water temperature.
  • PLC control, powerful function, simple operation, can be selected with a variety of communication protocols

Description

  1. Represent air-cooledchiller unit
  2. Indicateunit nominal refrigerating capacity(USRT)
  3. S= single compressor  D= double compressor
  4. Refrigerant type
  5. Blank=dry evaporator; FT=floodedevaporator; FF=falling film evaporator
  • Using environmental protection R407C or R134a, OPD value is zero, and will not destroy the ozone layer.
  • The condenser heat exchange tube adopts 5mm diameter copper tube, which is more efficient, and greatly reduce the amount of refrigerant filling.
  • It only needs to connect the chilled water pipe and power supply on site, which can effectively shorten the installation period.
  • COP of fallingfilm type unit is up to 3.4 or above, it can meet first level energy efficiency standards.
  • Stepless energy regulation, accurate control of water temperature.
  • PLC control, powerful function, simple operation, can be selected with a variety of communication protocols
Unit model AC-071S-
R407C
AC-100S-
R407C
AC-127S-R407C AC-160S-
R407C
AC-177S-
R407C
AC-217S-
R407C
AC-240S-
R407C
AC-094D-
R407C
AC-121D-
R407C
AC-142D-
R407C
AC-179D-
R407C
AC-211D-
R407C
AC-253D-
R407C
Rated cooling
capacity
kW 250 351 445 562 623 762 845 338 425 500 628 743 890
USRT 71.1 99.7 126.6 159.8 177.1 216.7 240.1 96.2 120.8 142.2 178.5 2113 253.1
Refrigerant R407C
Power 380V-415V/3PH/50Hz
Rated power kW 86 121 156 200 215 268 294 120 149 172 221 263 312
Unit installation current A 204 290 335 388 431 550 635 270 324 408 532 590 670
Unit starting current A 289 388 481 562 684 908 1075 325 430 490 619 680 812
Total COP 2.90 2.89 2.85 2.81 2.89 2.84 2.87 2.82 2.86 2.90 2.85 2.82 2.85
Evaporator form Dry type evaporator
Chilled water flow l/s 12.0 16.8 21.3 26.9 29.8 36.5 40.4 16.2 20.3 23.9 30.0 35.6 42.6
Chilled water side interface Φ3″ Φ4″ Φ4″ Φ5″ Φ5″ Φ6″ Φ6″ Φ4″ Φ4″ Φ5″ Φ5″ Φ6″ Φ6″
Unit N.W. kg 3145 3574 4228 5492 6072 6977 8067 3804 4358 4903 6101 6796 8010
Unit dimensions (Height) 2250 2250 2250 2250 2250 2250 2250 2250 2250 2250 2250 2250 2250
(Breadth) 2250 2250 2250 2250 2250 2250 2250 2250 2250 2250 2250 2250 2250
(Length) 3250 4250 5250 6250 7250 8250 9250 4250 5250 6250 7250 8250 10250

Remark:

1.Evaporator in and out of the water temperature: 7℃/12℃;

2. environment temperature: 35℃;

3.evaporator water side fouling factor: 0.018m2.k/kw, superscript current and power based on 380V/3PH/50Hz.

Unit model AC-081S-R134a-FF AC-109S-R134a-FF AC-137S-R134a-FF AC-177S-R134a-FF AC-217S-R134a-FF AC-257S-R134a-FF AC-314S-R134a-FF AC-066D-R134a-FF AC-105D-R134a-FF AC-116D-R134a-FF AC-152D-R134a-FF AC-195D-R134a-FF AC-218D-R134a-FF AC-274D-R134a-FF
Rated cooling
capacity
kW 284 383 481 621 763 904 1106 233 369 408 533 686 767 962
USRT 80.7 109 136.8 176.7 217 256.9 314.4 66.2 104.9 116.1 151.5 195 218 273.5
Refrigerant R134a
Power 380V-415V/3PH/50Hz
Rated power kW 83 111 138 178 224 265 321 68 108 117 154 200 221 277
Unit installation current A 209 282 342 484 597 666 748 234 272 288 408 490 564 684
Unit starting current A 289 374 481 735 982 1219 1393 264 337 348 490 543 653 819
Total COP 3.42 3.47 3.48 3.48 3.41 3.41 3.44 3.41 3.41 3.50 3.46 3.43 3.47 3.48
Evaporator form Dry type evaporator
Chilled water flow l/s 13.6 18.3 23.0 29.7 36.5 43.2 52.9 11.1 17.6 19.5 25.5 32.8 36.7 46.0
Chilled water side interface Φ4″ Φ4″ Φ6″ Φ6″ Φ6″ Φ6″ Φ8″ Φ3″ Φ4″ Φ4″ Φ5″ Φ6″ Φ6″ Φ6″
Unit N.W. kg 2990 3775 4868 6107 7382 9266 1188 3346 4019 4856 5672 6648 7359 9607
Unit dimensions (Height) 2250 2250 2250 2250 2250 2250 2250 2250 2250 2250 2250 2250 2250 2250
(Breadth) 2250 2250 2250 2250 2250 2250 2250 2250 2250 2250 2250 2250 2250 2250
(Length) 3250 4250 5250 6250 7250 8250 9250 3250 4250 5250 6250 7250 8250 10250

Remark:

1.Evaporator in and out of the water temperature: 7℃/12℃;

2. environment temperature: 35℃;

3.evaporator water side fouling factor: 0.018m2.k/kw, superscript current and power based on 380V/3PH/50Hz.

Get Quote

Contact Us

Quote Now